How cables and wires are made
Copper or aluminium rod is drawn down to fine wire, annealed, and bunched or stranded into a conductor. The conductor passes through an extruder that applies PVC, XLPE, rubber or a halogen-free compound as insulation. A spark tester sits on the line after the extruder and applies a high voltage to the surface: any pinhole or thin spot sparks and the fault is logged or cut out. Cores are then laid up together, fillers and armour added for power cable, and an outer sheath extruded. XLPE is cured after extrusion. Finished lengths are wound into coils or onto drums, high-voltage tested, printed and packed.
Two things drive cost: the weight of metal in the conductor and the weight of compound around it. Both are also where shortcuts appear. India exported US$2,871.3 million under HS 8544 in FY2025-26 according to Department of Commerce TradeStat; the figure is provisional, and the heading includes winding wire, wiring harnesses and optical fibre cable as well as power and building cable. We have not found an official source naming cable clusters, so we name no town.
What we check on cables and wires
| Check | How it is checked | What fails |
|---|---|---|
| Conductor resistance | Factory measures a sample length from a coil we pick on its resistance bridge; reading corrected to 20 °C and compared with the IEC 60228 maximum for the size and class | Resistance above the maximum: the conductor is undersized or of poorer metal |
| Conductor material and build | Cut end examined; strand count and strand diameter compared with the class and the datasheet | Copper-clad aluminium supplied as copper; fewer strands than declared |
| Insulation and sheath thickness | Thin slices cut and measured on the factory's measuring projector or microscope; average and minimum compared with the cable standard | Minimum point below the limit; eccentric insulation |
| Spark test | Spark tester on the extrusion line seen running; set voltage and fault counter checked, with the tester's calibration record | Tester switched off, set too low or not calibrated |
| High-voltage test | Finished coils or drums tested in the factory's HV bay, with test voltage and time recorded | Breakdown, or test not done on finished lengths |
| Length | Sampled coils measured on a metering rewinder or by metre marks; coils weighed against the nominal weight per length | Coil shorter than labelled |
| Print marking | Standard, size, voltage, cores, maker, year, Euroclass, HAR or BASEC marks and metre marks read along the length | Mark that the certificate does not support; print that rubs off |
| Core colours and construction | Core colours, number of cores, earth core, armour and fillers checked against the specification | Wrong colour code for the market; earth core missing or undersized |
Euroclass, BASEC and UL: what the documents must cover
In the EU, power, control and communication cables installed permanently in buildings are construction products. EN 50575 sets their reaction-to-fire performance and classes them from Aca, the best, to Fca, with extra classes for smoke (s), flaming droplets (d) and acidity (a). The manufacturer issues a Declaration of Performance and marks CE. Under Commission Decision 2011/284/EU, classes Aca, B1ca, B2ca and Cca need a notified certification body that type-tests the cable and audits the factory twice a year; Dca and Eca need a notified laboratory for the initial type test. Regulation (EU) 2024/3110 has applied since 8 January 2026 and replaces Regulation (EU) No 305/2011 in stages; the existing harmonised standards stay in use during the transition.
The inspector does not classify fire performance. We read the classification report and certificate of constancy of performance, check that they name the same cable type, construction and compound, and compare the Euroclass printed on the cable and drum label with the Declaration of Performance. A cable printed Cca-s1,d1,a1 must have a certificate for exactly that construction.
In the UK, BASEC certifies cables against British Standards such as BS 6004 and BS 6724 and audits the factory. In the US and Canada, building wire is listed by a certification body to standards such as UL 44 (thermoset) and UL 83 (thermoplastic). In each case we check the certificate or listing directory for the factory, the cable type and the size range, because a certificate for one factory does not cover cable bought in from another. See UL and ETL listing and UKCA and CE marking.
Common defects in cables and wires
| Defect | Why it matters | Class |
|---|---|---|
| Conductor resistance above the IEC 60228 maximum | Cable overheats at its rated current | Critical |
| Copper-clad aluminium sold as copper | Higher resistance, weaker terminations, fraud | Critical |
| HV breakdown on a finished length | Insulation fault that can reach the user | Critical |
| Euroclass, HAR, BASEC or UL marking without a matching certificate | Cable cannot lawfully be sold or installed as marked | Critical |
| Insulation below the minimum thickness | Reduced safety margin; fails type requirements | Major |
| Coil or drum short of the labelled length | Buyer pays for cable not received | Major |
| Wrong core colours for the market | Wiring errors on site | Major |
| Print illegible or rubs off | Cable cannot be identified after installation | Minor |
| Sheath scuffs, uneven coil winding | Appearance and handling | Minor |
RoHS and REACH apply to cable compounds sold in the EU; lead stabilisers in PVC are the usual concern. These need a lab result on the compound or cable, not a visual check. See RoHS and WEEE.
Packing, transit and your purchase order
Building wire travels in shrink-wrapped coils in cartons; power cable on wooden or steel drums. Cable ends should be sealed with caps so water cannot enter the conductor, drums should carry the length, type, gross weight and an arrow for the rolling direction, and drum battens should protect the outer layer. Wooden drums for export need ISPM 15 treatment and marking; see ISPM 15. At loading, drums are chocked so they cannot roll.
Put these in your purchase order:
- Cable standard, type, size, number of cores, voltage rating and conductor class.
- Conductor metal: plain or tinned copper, or aluminium; copper-clad aluminium not accepted unless stated.
- Insulation and sheath compound, colours and Euroclass or approval marks required.
- Print legend, metre marking and coil or drum length with tolerance.
- Routine tests to witness: conductor resistance, spark test, HV test, and how many lengths.
- Certificates to supply: Declaration of Performance and classification documents, BASEC or UL listing, RoHS report.
- Packing: coil wrap, carton marks, drum type, end caps and ISPM 15.
Book an inspection anywhere in India.
Sources
- Department of Commerce, TradeStat: commodity-wise exports (HS 8544, FY2025-26 provisional)
- IEC 60228:2023, Conductors of insulated cables (IEC webstore)
- Commission Decision 2011/284/EU, attestation of conformity for power, control and communication cables (EUR-Lex)
- Regulation (EU) 2024/3110, Construction Products Regulation (EUR-Lex)
- BASEC: CPR testing and certification